Triggers, falling vs rising and PLC startup yields different behavior
- Authors
- Name
- Kassym Dorsel
Introduction
Triggers are one of the basic building blocks for any PLC and even general programing. It allows you to run a function or routine once on a condition change. For example sending an alarm to the HMI or sending an event to a database. For a trigger to work it requires a change in condition or an edge. This is the reason for calling it an edge detector.
They can be either falling edge triggers or rising edge triggers. Beckhoff has both built in as F_TRIG
and R_TRIG
function blocks.
Comparison
One may expect that a negated input to an F_TRIG
would yield the same result as an R_TRIG
and vice versa. As expected the following will yield the same results with rcnt = fcnt
.
rtrig : R_TRIG;
ftrig : F_TRIG;
in1 : BOOL := FALSE;
rcnt : INT;
fcnt : INT;
rtrig(CLK := in1);
IF rtrig.Q THEN
rcnt := rcnt + 1;
END_IF
ftrig(CLK := NOT in1);
IF ftrig.Q THEN
fcnt := fcnt + 1;
END_IF
We can also look at this in the opposite way, this being a falling edge detector. It will also yield the same results.
rtrig2 : R_TRIG;
ftrig2 : F_TRIG;
in2 : BOOL := TRUE;
rcnt2 : INT;
fcnt2 : INT;
rtrig2(CLK := NOT in2);
IF rtrig2.Q THEN
rcnt2 := rcnt2 + 1;
END_IF
ftrig2(CLK := in2);
IF ftrig2.Q THEN
fcnt2 := fcnt2 + 1;
END_IF
PLC Startup
Now, as I've mentioned above, a trigger requires an edge to work correctly. What happens on the first PLC scan after starting up the PLC and the input is already at the resulting edge logic to normally create a trigger? This is not a common occurrence, but it can happen. For example after a power outage.
Looking at the result from the above code gives the expected result. However if a small change is made the behavior is no longer the same. The change below has the initial values of in1
and in2
swapped.
rtrig : R_TRIG;
ftrig : F_TRIG;
in1 : BOOL := TRUE;
rcnt : INT;
fcnt : INT;
rtrig2 : R_TRIG;
ftrig2 : F_TRIG;
in2 : BOOL := FALSE;
rcnt2 : INT;
fcnt2 : INT;
rtrig(CLK := in1);
IF rtrig.Q THEN
rcnt := rcnt + 1;
END_IF
ftrig(CLK := NOT in1);
IF ftrig.Q THEN
fcnt := fcnt + 1;
END_IF
rtrig2(CLK := NOT in2);
IF rtrig2.Q THEN
rcnt2 := rcnt2 + 1;
END_IF
ftrig2(CLK := in2);
IF ftrig2.Q THEN
fcnt2 := fcnt2 + 1;
END_IF
After the first PLC cycle rcnt1 = rcnt2 = 1
whereas fcnt1 = fcnt2 = 0
.
Conclusion
During normal operation the behavior of R_TRIG
and F_TRIG
are interchangeable by inverting the logic of the input. However this is no longer true during the first PLC cycle.
On a first PLC cycle if the input to a R_TRIG
is true, the R_TRIG
will consider that being an edge and set its output Q
to true for that first cycle.
On a first PLC cycle if the input to a F_TRIG
is false, the F_TRIG
will NOT consider that being an edge and it wil keep its output Q
set to false.
One common use of triggers is for errors or warnings. When integrating an external device there is normally an error signal. This signal can be NC or NO. In the NO variant a R_TRIG
would be used to catch the error. In an NC variant a F_TRIG
would be the default.
For example given a device with a NC error signal connected to a PLC. After a power outage the device starts up faster than the PLC (this is common) and sets its error output to false (meaning there is an error). Using and F_TRIG
once the PLC starts, it would not trigger and would not take the necessary steps to warn the operator resulting in troubleshooting downtime. Whereas if a R_TRIG
had been used with an inverted input, the operator would have been correctly warned.
This examples makes assumptions on the structure of error reporting. However the fact remains that the way R_TRIG
and F_TRIG
work are not inversely identical on the first PLC cycle.
This behavior was tested on builds 4022.32 and 4024.12 with the exact same results. I don't know how similar triggers work on different PLCs, but be weary of how your triggers work on the first PLC scan!